Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T01CM02566
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
| 08/09/2001 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*1.) ABS DWV ON NORTH SIDE BATHROOMS OK FIRST & SECOND FLOOR COPPER OK PRESSURE TEST OK 2.) NEED TO SEE VTR & CLEAN OUT OUTSIDE BATHROOMS. 3.) OK TO COVER WALLS. | |
| 06/19/2001 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*NO CHANGE ON ROUGH IN | |
| 06/17/2001 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000* | |
| 06/15/2001 | PLUMBING - ROUGH, SOIL | Partial Approval | 1. CORRECT BACKPITCH ON 3" DRAIN 2.) PROVIDE FULL SIZE C.O ON 3" BRANCH 3.) WATER TEST TO SOUTHEND CONNECTION OK 4.) WILL PROVIDE SEPARATE TEST TO OFFICE WHEN PIPED 5.) I WANT TO SEE FINAL TIE-IN TO EXISTING 7.) DONT FORGET PLAN REVISION FOR Z SINKS AT NW CORNER. 8) OK TO COVER | |
| 06/13/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*1. I NEED TO SEE THE INSPECTION HISTORY FOR SHELL BLDG. 2. EXISTING 4" CUT OUR & NOT REPLACED. 3. PLUMBING NOT INSTALLED PER PLAN. 4. WATER TEST REQUIRED IS 10 FOOT HEAD. | |
| 06/12/2001 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* |