Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM02566
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2002 | ELECTRIC - CABLE DROP | Approved | ||
| 08/27/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*1. WILL NEED OFFICE TO EXAMINE CONTENTS OF LETTER ON ACCEPTANCE OF (A) SQUARE 'D" SIDE ENTRY INTO SWITHGEAR NOT NORMALLY DESIGNED FOR SIDE ENTRY (B) NEED LETTER DESCRIBING METHOD OF GROUNDING TO USE (UFER MISSED) (C) SHOW DERATE OF CONDUCTORS FOR EXTERIOR FEEDER .2. BOLT DOWN SWITCH GEAR 3. TEMP LETTER AT OFFICE. | |
| 08/24/2001 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000*SERVICE C NOT READY | |
| 08/21/2001 | ELECTRIC - CABLE DROP | Partial Approval | CABLE DROP AND TEMP POWER. RECEIVED LETTER FROM SQUARE D APPROVING THE BOTTOM PORTION, SIDE ENTRANCE OF SERVICE SECTION TO BE USED AS AN ENTRY FOR THE PANEL FEEDER CONDUIT-NEED LETTER FROM SQUARE D OUTLINEING PROCEDURE AND MATERIAL TO BE USED FOR CLEANING OF CONTAINATED BUS * NEED APPROVED LETTER FROM ENGINEER OF RECORD DETAILING THE TRANSFORMER SECONDARY WIRE SIZE, AMOUNT OF WIRER AND TYPE OF WIRER TO BE USED IN EVERY SERVICE SECTION. THE CONCRETE ENCLOSED ELECTRADE WAS NOT INSTALLED WILL NEED ENGINEER LETTER ON ALTERNATE GROUND METHOD EG. 2 RODS 6" APART PLEASE SHOW DERATING CALCS AND APPROVED OF FEEDER CONDUIT IN DIRECT SUN LIGHT NEED LETTER OF TORQUING EACH SERVICE MAIN BAND JUMPER AND NEUTRAL DISCONNECT LINK TO BE MARKED. |