Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM02566
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2001 | ELECTRIC - ABOVE CEILING | Approved | ABOVE CEILING BUILD D 1ST AND 2ND FLOOR APPROVED PLEASE EXPOSED ALL AIR HANDLING METER AHU 5 IMPROPER WIRE SIZE IMPROPER WIRING METHOD MARK ON NAME PLATE ALL AUXILARY DEVICES BEING UTILIZED INSTALL COVER. | |
| 07/18/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | 1.)PLATEFORM PANEL BOARD LOCATED BELOW FOREIGN PIPING MUST COMPLY W/CODE 110-26 2.) COVER ALL PANEL BOARDS TO KEEP DEBRIS AWAY FROM BUSSING. 3.) ADITORIUM/CAFETERIA ROUGH ELECTRIC APPROVED. 4.) FIRST FLOOR CONDUIT PANEL FEEDERS APPROVED. EXCEPT KITCHEN AREA. 5.) 2ND FLOOR PANEL BOARD FEEDER APPROVED EXCEPT. 205 AND 206. | |
| 07/16/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*ROUGH WALL COMPUTER ROOM,BATHROOM. | |
| 07/10/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | #3 AND #4 WALK APPROVED. | |
| 07/06/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | WALLS PARTIAL RMS 208-209-210 WALLS ONLY OK TO COVER WALLS LEAVE PNL AREAS OPEN ABOVE PNL FOR HOME RUNS STRAP CONDUITS BY SWITCH | |
| 07/03/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*O.K PANEL E-8,E-7,E-6,E-5,E-1,E-2,E3 & E-4 OK TO COVER LIBRARY WALK APPROVED 2ND FL NORTH 1ST FL NORTH BATHROOM APPROVED. CLASSROOM 212 CLASSR00M211 |