Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM02545
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
04/11/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) WATER HEATER FURNACE MISSING WEATHER CAPS 2) ELECTRIC SERVICE REQUIRES NON WATER BOND LABEL 3) BACK WATER VALVE MUST BE ACCESSIBLE 4) PROVIDE PHYSICAL BARRIER BETWEEN BLOWN IN INSUALTION ( 12" ABOVE INSULATION TOP) AND FURNACE 5) PROVIDE SWAY RESTRAINT ON SUSPENDED FURNACE 6) INADEQUATE INSULATION BELOW FURNACE PLATFORM |