Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2002 |
PLUMBING - ABOVE CEILING |
|
Approved |
|
| 09/17/2002 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) RAIN LEADER WATER TEST IS OK 2.) MUST PROVIDE WATER TEST ON WASTE & VENT SYSTEM ALL THE WAY TO TOP OF VENTS. 3.) MUST PROVIDE HANGERS ON ALL HORIZONTAL RAIN LEADERS 18" FROM COUPLINGS BOTH SIDES. 4.) WILL REQUIRE ARCHITECH TO CALEULATE BTU & CFH DEMAND ON P.O.C. OF NEW 1 1/4" GAS LINE TO 1 1/2" EXSISTING GAS LINE. |