Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM02498
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/24/2001 | FRAMING | Denied | IVRS - Inspection 0999*1.) NAIL PROTECT A/C AT WH. PLATFORM 2.) FIRE BLOCK GARGAE 2 LOCATION 3.) WALL AT H2 SHEAR WALL NAILING FURRING AT 6" ON 4.) STAIR NOT PER 4/SD3 5.) 3-2X POST REG FAMILY. 6.) LIVING RM G.L.B. REQUIRES POST PER NOTE 24 7.) PROVIDE SPACE FOR INSULATIONS AT ATTIC FURANCE. 8.) DROP CEILING 2ND FLOOR FURNACE 9.) FIRE STOP W/H VENT CHASE. 10.) NAIL PROTECT DWV PLUMBING DWV NOT GLUED. 11.) SAN "T" NOT ALLOWED IN HORIZONTAL 12. M.B.R. POST 23. |