Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/30/2001 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PARTIAL PENDING INSTALL OF OVEN, STUCCO AND INSULATION CERTIFICATES |
| 10/24/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SEWER CLEANOUTS MUST BE TERMINATED WITH THREADED CLEANOUT PLUGS OR CAPS 2) INSTALL RAIN HOOD AT DRYER VENT 3) INSTALL COUNTER TOPS AND PLUMBING FIXTURES 4) INSTALL OVEN 5) INSTALL DISHWASHER 6) SEAL HOLE AT R.A. PLATFORM 7) ALL GARAGE OUTLETS MUST BE GFCI PROTECTED 8) CORD AT HYDRO TUB NOT PER CODE 9) GARAGE LIGHTS MUST BE INSTALLED OR TERMINATE IN ELECTRIC BOX 10) FIRE CAULK GAS LINE IN FIREPLACE 11) A/C DISCONNECT NOT PERMITTED BEHIND UNIT MINIMUM 30" SPACE REQUIRED 12) GAS BOND IS REQUIRED |