Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02451
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2001 | ELECTRIC - FINAL | Approved | OK FINAL. | |
10/01/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) LIGHTING CIRCUIT AND EMGENCY LIGHTING TO BE ON SAME CIRCUIT 700-12. 2.) EXPOSED CONDUCTORS IN ATTIC PLACE IN JUNCTION BOX OR REMOVE. | |
09/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED REJECTION CUPS 2.) CLEAN SURFACE UNDERGROUNDING LUG 250-12 3.) PLEASE PROVIDE WETHER PROOF COVER OR GFCI PROTECTION FOR RECEPTACLE BY WASH SINK AND DRAIN. 4.) NEED DISCONNECTING MEANS FOR WATER HEATER 5.) SECURE LIGHTING TRANSFORMERS 6.) BROKEN M/C CABLE SHEATHING 7.) STRAP M/C CABLE AS PER CODE ABOVE CEILING. 8.) EMGENCY LIGHTING TO BE ON LIGHTING CIRCUIT 700-12. |