Permit: T01CM02451

Parcel: 117150050


Addresses:

110 E CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02451

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2001 ELECTRIC - FINAL Approved OK FINAL.
10/01/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) LIGHTING CIRCUIT AND EMGENCY LIGHTING TO BE ON SAME CIRCUIT 700-12. 2.) EXPOSED CONDUCTORS IN ATTIC PLACE IN JUNCTION BOX OR REMOVE.
09/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) NEED REJECTION CUPS 2.) CLEAN SURFACE UNDERGROUNDING LUG 250-12 3.) PLEASE PROVIDE WETHER PROOF COVER OR GFCI PROTECTION FOR RECEPTACLE BY WASH SINK AND DRAIN. 4.) NEED DISCONNECTING MEANS FOR WATER HEATER 5.) SECURE LIGHTING TRANSFORMERS 6.) BROKEN M/C CABLE SHEATHING 7.) STRAP M/C CABLE AS PER CODE ABOVE CEILING. 8.) EMGENCY LIGHTING TO BE ON LIGHTING CIRCUIT 700-12.