Permit: T01CM02422

Parcel: 133152880

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/25/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*