Permit: T01CM02388

Parcel: 140100190


Addresses:

2935 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM02388

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*T01CM02388
02/21/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*CORRECTIONS NEEDED. 1.) THE UFER GROUNDING CONDUCTOR MUST BE TERMINATED TO THE NEUTRAL (GROUNDED) BAR. THE METAL OF THE CAN SHOULD NOT CONDUCT ANY FAULT CURRENT. 2.) PUT ADDRESS LABEL ON METER. SCREW OR RIVET ALL LABELS TO CANS 3.) INSTALL BLANK COVER ON TOP METER HUB. 4.) CHANGE #4 WIRE TO #3 FOR FEED TO 100A SWITCH #4 IS ALLOWED AT 100AMPS FOR RESIDENTIAL SERVICE ENTRANCE CONDUCTORS ONLY. 5.) INSTALL GROUNDING BUSHING ON 11/2" CONDUIT FEEDING OUT OF CARETAKER SWITCH. CODE RULE IF CONDUCTORS #4 OR LARGER.