Permit: T01CM02386

Parcel: 124172210

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/11/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
09/10/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) NEED TO INSTALL ANTI-SIPHON ON HOSE BIBS 2) T&P LINE NOT INSTALL TO CODE MUST TERMINATE 6" ABOVE GRADE LEVEL 3) CLEAN OUT MUST BE AT GRADE LEVEL 4) VENT THRU ROOF MUST BE 3' ABOVE COOLER