Permit: T01CM02376

Parcel: 137338000

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/11/2001 FRAMING Approved IVRS - Inspection 0000*
07/10/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE 1" CLEARANCE FROM COMBUSTIBLE MATERIAL AT FURNACE FLUE PIPE AND CHIMNEY FLUE AND UNIT 2) SEAL RACEWAYS AT PANEL AND ISLAND PENNINSULA 3) INTERIOR ENGINEERED BRACED WALLS OVER KNOTCHED 4) SEAL WEATHER BARRIER TURN BEHIND CHIMNEY
07/05/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) SEE NOTES FROM PREVIOUS INSPECTION 2) ITEMS REQUESTED NOT CORRECTED
07/03/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE EXPANSION BOLTS AT ENTRY AND THRU OUT SINGLE SOLE PLATE SEE UBC 1806.6 2) DRY IN ROOF IN ORDER TO VARIFY COMBUSTIBLE MATERIAL CLEARNACE, INSTALL FLASHING ETC... 3) PROVIDE 30 INCH CLEARANCE WORK SPACE AT HORIZONTAL FURNACE IN ATTIC 4) ISOLATE AND SECURE PEX FROM FRAMING BRACE IN GARAGE 5) DUCT IN KITCHEN NOT SIZED PER PLAN 6) SEAL ISLAND PENNINSULA PVC AT FLOOR