Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM02349

Parcel: 12201006B


Addresses:

4676 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02349

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/12/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) DISCONNECT ON ROOF FOR NEW AC UNIT NOT IN COMPLIANCE OF WORKING CLEARANCE 110-26 N.E.C. 2.) LABEL DISCONNECT AT SERVICE 230-70 AND PANELS 3.) APPLIANCES AND EQUIPMENT TO COMPLY WITH ART 422-30 N.E.C.