Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 09/21/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) MC CABLE TO BE SUPPORTED WITHIN 12" OF J-BOXES PER N.E.C. 2.) USE APPROVED LISTED STRAPS FOR MC CABLE, CONDUIT STRAPS ARE OVER SIZED, NOT PROVIDING SEZURE SUPPORT AS STATED IN N.E.C. |
| 09/17/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL 1.) FRONT SALES AREA OK 2.) CALL FOR BACK AREA INSPECTION WHEN WORK IS COMPLETED. |