Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM02349

Parcel: 12201006B


Addresses:

4676 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM02349

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
09/21/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*NOTES 1.) MC CABLE TO BE SUPPORTED WITHIN 12" OF J-BOXES PER N.E.C. 2.) USE APPROVED LISTED STRAPS FOR MC CABLE, CONDUIT STRAPS ARE OVER SIZED, NOT PROVIDING SEZURE SUPPORT AS STATED IN N.E.C.
09/17/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*PARTIAL 1.) FRONT SALES AREA OK 2.) CALL FOR BACK AREA INSPECTION WHEN WORK IS COMPLETED.