Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2001 |
ELECTRIC - UNDERGROUND |
|
Approved |
|
| 10/07/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK 3/4 PVC AROUND BUILDING EXCEPT AT SIDE WALK EAST SIDE MEET REQUIREMENT OF 300-5 |
| 10/04/2001 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*1.)U.G. ELECTRIC TO BE 24" BELOW FINISHED GRADE IN DRIVEWAYS, PARKING LOTS, 300-5 N.E.C. |
| 09/14/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK SECONDARY CONDUITS UP TO BLD EXIST SERVICE EXCEPT WHERE 90 STUB UP NOT INSTALLED YET, ALSO NOTE THAT A REVISION IS IN PROGRESS OF SERVICE INSTALLATION. |
| 07/27/2001 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000* |