Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T01CM02349
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2001 | ELECTRIC - UNDERGROUND | Approved | ||
| 10/07/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*OK 3/4 PVC AROUND BUILDING EXCEPT AT SIDE WALK EAST SIDE MEET REQUIREMENT OF 300-5 | |
| 10/04/2001 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0245*1.)U.G. ELECTRIC TO BE 24" BELOW FINISHED GRADE IN DRIVEWAYS, PARKING LOTS, 300-5 N.E.C. | |
| 09/14/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*NOTES OK SECONDARY CONDUITS UP TO BLD EXIST SERVICE EXCEPT WHERE 90 STUB UP NOT INSTALLED YET, ALSO NOTE THAT A REVISION IS IN PROGRESS OF SERVICE INSTALLATION. | |
| 07/27/2001 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000* |