Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T01CM02335
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2001 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
06/12/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF FOOTING AND FOUNDATION INSPECTION OR EXPOSE FOOTING TO A DEPTH OF 12" AND EXPOSE REINFORCING STEEL IN ONE LOCATION, 2 BARS 2) PLAN CALLS FOR 6'-8" TO SOUTH PROPERTY LINE ONLY 5'-11" EXISTS TO FENCE, EITHER REVISE PLAN TO ASBUILT AND HAVE APPROVED OR PROVIDE PROPERTY PINS AT TWO SOUTH CORNERS 3) HD2A HOLD DOWNS NOT INSTALLED 4) UNTREATED LUMBER CANNOT BE IN CONTACT WITH CONCRETE 5) PROVIDE CITY OF TUCSON APPROVED TRUSS DRAWINGS 6) EXTERIOR SHEATHIN MUST BE NAILED TO ALL FRAME MEMBERS PER CODE 7) PLAN CALLS FOR MAXIMUM HEIGHT OF BUILDING TO RIDGE 10'-0" ACTUAL HEIGHT 12'-5" 8) SHEATHIN NOT PROPERLY NAILED 9) PROVIDE HEADER REQUIREMENT FOR 16'-0" DOOR |