Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02321
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
09/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE PROPER PAPERWORK FOR REJECTION CLIPS INSTALLED 2.) WIRING TO DEVICES WRAPPED IN WRONG DIRECTION 3.) NO MAINTANCE RECEPTACLE IN ROOF TOP TO SERVICE RESPECTIVE UNITE. 4.) LOCK COLOR CODEING TO A/C FEEDER. | |
09/06/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.STRAP CONDUIT ABOVE PANEL AS PER CODE. 2.) USE LISTED NIPPLE 3.) NEED REJECTION CLIPS. 4.) CAN NOT USE SHEET METAL SCREWS 250-12 DISCONNECTS & GUTTER 5.) NOTE #5 ON PLAN STATES NOT TO COMBINDE HOME RUNS 6.) GROUND NEED TO BE SPLICED AS PER CODE AND ATTACHED TO BOXES 7.) LOOSE SEAL TITE FITTINGS AT INSTALL HOT. * CHECK ROOF & SERVICE GUTTER NEXT INSPECTION. | |
09/05/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |