Permit: T01CM02321

Parcel: 120052730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02321

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE PROPER PAPERWORK FOR REJECTION CLIPS INSTALLED 2.) WIRING TO DEVICES WRAPPED IN WRONG DIRECTION 3.) NO MAINTANCE RECEPTACLE IN ROOF TOP TO SERVICE RESPECTIVE UNITE. 4.) LOCK COLOR CODEING TO A/C FEEDER.
09/06/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.STRAP CONDUIT ABOVE PANEL AS PER CODE. 2.) USE LISTED NIPPLE 3.) NEED REJECTION CLIPS. 4.) CAN NOT USE SHEET METAL SCREWS 250-12 DISCONNECTS & GUTTER 5.) NOTE #5 ON PLAN STATES NOT TO COMBINDE HOME RUNS 6.) GROUND NEED TO BE SPLICED AS PER CODE AND ATTACHED TO BOXES 7.) LOOSE SEAL TITE FITTINGS AT INSTALL HOT. * CHECK ROOF & SERVICE GUTTER NEXT INSPECTION.
09/05/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*