Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/11/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/10/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE PROPER PAPER LINE FOR REJECTION CLIP INSTALLED. 2.) WIRING TO DEVICE WRAPPED IN THE WRONG DIRECTION. 3.) NO MAINT RECEPTACLE IN ROOF TOP TO SERVICE RESPECTIVE UNITS. 4.0 COLOR CODE A/C FEEDER. |
| 09/07/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
CANCELLED. |
| 09/06/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) USE LISTED NIPPLE 2.) NEED REJECTION CLIPS 3.) CAN NOT USE SHEET METAL SCREWS 250-12 DISCONNECTS & GUTTER. 4.) LOOSE SEALTITE FITTINGS AT INSTALL HOT 5.) STRAP CONDUIT ABOVE PANEL AS PER CODE. 6.) NOTE #5 ON PLAN STATES NOT TO COMBINED 7.) GROUND NEED TO BE SPLICED AS PER CODE AND ATTACHED TO BOXES * CHECK ROOF & SERVICE GUTER NEXT INSPECTION. |