Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02320

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE PROPER PAPER LINE FOR REJECTION CLIP INSTALLED. 2.) WIRING TO DEVICE WRAPPED IN THE WRONG DIRECTION. 3.) NO MAINT RECEPTACLE IN ROOF TOP TO SERVICE RESPECTIVE UNITS. 4.0 COLOR CODE A/C FEEDER.
09/07/2001 ELECTRIC - FINAL Not ready for Inspection CANCELLED.
09/06/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) USE LISTED NIPPLE 2.) NEED REJECTION CLIPS 3.) CAN NOT USE SHEET METAL SCREWS 250-12 DISCONNECTS & GUTTER. 4.) LOOSE SEALTITE FITTINGS AT INSTALL HOT 5.) STRAP CONDUIT ABOVE PANEL AS PER CODE. 6.) NOTE #5 ON PLAN STATES NOT TO COMBINED 7.) GROUND NEED TO BE SPLICED AS PER CODE AND ATTACHED TO BOXES * CHECK ROOF & SERVICE GUTER NEXT INSPECTION.