Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/2001 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
|
| 07/31/2001 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
1.) MEDIUM PRESSURE GAS TO BE TESTED AT 60# FOR 30 MINUTES. 2.) INSTALL UNIONS ON CONDENSATE DRAINS. 3.) EXISTING SYSTEM NEEDS SOME WORK 1.) BLOCKING INADEQUETE AND NEEDS REPAIRING IN PLACES 2.) ALL VALVES TO BE AGA OR CSA APPROVED. 3.) ALL REGULATORS TO BE INSTALLED TO CODE. |