Permit: T01CM02294

Parcel: 110066320

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T01CM02294

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*/ 1) PER CONVERSATION WITH FRANK GREER AND HIS INITIALS ON THE INSPECTION CARD I HAVE CONFIRMED THE ROUGH PLUMBING, YARD WATER AND HCS CONNECTION FOR THIS PROJECT WAS INSPECTED AND APPROVED 9/12/01 BY FRANK GREER AND THE INSPECTION REPORT WAS LOST. APPROVED THIS DAY 11/08/01 JRIVA
11/02/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*DO NOT COVER AND RECALL FOR INSPECTION. 1.) ALL COVERED WORK THAT HAS NOT BEEN APPROVED IN WRITING MUST BE EXPOSED. DO NOT CONTINUE. EXPOSE ALL PLUMBING INCLUDING: ROUGH/SOIL AND SEWER/HCS/YARDWATER.
09/12/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) BOTH THE BUILDING DRAIN AND THE BUILDING SEWER REQUIRE A PITCH OF AT LEAST 2%. CORRECT BACKPITCH AND RE-CALL FOR INSPECTION. 2.) HCS/SEWER CONNECTION DENIED BECAUSE I STILL WANT TO SEE THE WATER TEST AFTER CORRECTIONS ARE MADE.
09/11/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST TO THE TOP OF 10' HEAD 2.) MUST PROVIDE AIR OR WATER TEST ON YARD WATER LINE 3.) DO NOT COVER.