Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK C OF O. |
| 03/04/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) GROUND 8 X 8 J-BOX PER ART 250 N.E.C. 2.) INSTALL BOND BUSHING ON 3/4" CONDUIT WHERE USING R W'S AT CONNECTOR SUB PANEL. 3.) FILL IN BLANK AT SUB PANEL 250-94. 4.) INSTALL PERMANENT ADDRESS LABEL. |