Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/27/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. |
| 07/25/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1 PROVIDE AN OUTSIDE AIR VENT ON A/C EQUIPMENT 2.) MAKE DATA PLATE W/PROPER HEAT STRIP & FUSE UNIT ACCORDINGLY. 3.) HOOK UP HIGH & LOW VOTTAGE TO UNITS. OK FOR TEMP POWER. OK TO COVER CEILING. |
| 07/24/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*DUCT ABOVE CEILING NOT COMPLETE DUCTS HAVE BEEN ALTERED. OK TO COVER CEILING. LEAVE OUT TILES IN ROOM 106. PROVIDE SAFE ACCESS TO ROOF. ACCESS DOOR INSTALLED BACKWARDS. RECALL FOR FINAL. |