Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 04/24/2002 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000* |
| 04/22/2002 |
ELECTRIC - UFER |
|
Denied |
IVRS - Inspection 0999*/ 1) GROUND RODS COVERED WITHOUT INSPECTION EXPOSE TOP 6" OF EACH ROD FOR INSPECTION 2) OK TO DRYWALL INTERIOR NOTE: SILVER BACKED INSULATION FOAM NOT ALLOWED FOR CONTACT WITH STUCCO |
| 03/15/2002 |
ELECTRIC - UFER |
|
Denied |
IVRS - Inspection 0999*/ 1) GARAGE MUST HAVE A SEPERATE GROUND SYSTEM CONNECTED TO THE SUB PANEL. INSTALL TOW EACH 8' GROUND RODS 6 FEET APART CONNECTED TO SUB PANEL WITH A CONTINOUS #4 GROUND WIRE. NOT IN RISER YOU MAY USE EXISTING GROUND RODS BUT WITH A NEW CONDUCTOR ADDED TO SUB-PANEL NOTE: SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR 2) MAKE UP ALL GROUNDS IN BOXES |