Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/05/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/27/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/07/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) HAVE EXISTING ROOF BEAMS SIZED FOR SPAN 24" 6" X 6" X 20' SPAN 2) OUTLETS AT DINING ROOM 6' FROM DOOR |
| 02/04/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLUG HOLES IN TOP OF SUB-PANEL CABINET 2) OLD PORTION OF HOUSE WALLS REMOVED (OVERSPAN BEAMS) 3) MECH DUCT SOME CONNECTS ARE NOT DONE IN A WORKMANSHIP MANNER 4) MISSING OUTLETS ON INTERIOR WALL KIT-DINING ROOM 5) GAS PIPE/SUPPLY) IS OUT OF KITCHEN WALL 6) LOOSE MISSING STUDS AT NEW CLOSET, DINING ROOM 7) CENTER (ROMEX FEEDER) IN CENTER OF PIPE THEN SECURE TO SIDE OF ROOF JOIST (SHARP EDGE AT PIPE 8) MAKE SURE THAT BATHROOM OUTLET IS SUPPLIED BY A SEPERATE 20 AMP CIRCUIT 9) OUTLETS TO BE 6' MAXIMUM FROM ANY DOOR OR OPENING 10) PUT BATHROOM LIGHT IN A BOX 11) NEED COMB/RELIEF ARM FOR WATER HEATER 12) FIRE BLOCKING IS TO AT THE DROP CEILING NOT 4' 13) WATER HEATER FLUE NOT INSTALLED CORRECTLEY 14) HOLE IN EXISTING CMU WALL LEAVES BLOCK ABOVE UNSUPPORTED 15) BEAM CONNECTION TO MASONRY LENGTH NEED AN APPROVED DETAIL |