Permit: T01CM02257

Parcel: 121091750


Addresses:

2030 N ARCADIA AV

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
08/29/2001 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection 0000*
08/27/2001 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection 0000*/ 1) RASTRA WALL SECTION ON PLAN FTG NOT INSTALLED PER DETAIL 2) QUESTION WHAT HAPPENS AT WINDOW AND DOOR OPENINGS FOR VERTICAL REBAR? 3) KITCHEN SOIL LINE RUNNING PARALELL TO FOOTING LOWER PIPE OR RE ROUTE TO EXTREME RIGHT OR LEFT OF FTG