Permit: T01CM02245

Parcel: 111051290

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/21/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/14/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*CANNOT HAVE BACK TO BACK BOXES IN FIRE RATED PARTY WALL, MUST BE 24" APART MI AND IN DIFFERENT CELL UNLESS FIRE IS APPLYED PER LISTED INSTRUCTION.