Permit: T01CM02233

Parcel: 137338110

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/06/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
08/02/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*1.) COMPLETE AV FOR IRRIGATION 2.) PROVIDE 6 INCH CLEARENCE FROM EARTH @ HOT WATER TRL 3.) PROVIDE 36" FRONT CLEARANCE FROM AC CONDENSOR DISCONNECT 4.) LIGHT SWITCH INSTALLED IN ATTIC ACCESS OPENING 5.) COMBUSTIBLE MATERIAL WITHIN 1 INCH OF FLUE PIPE FURANCE.SEAL PENETRATIONS EXCEEDING 1/8" @ 911 ELEC BOXES 7.) EXHAUST FAN NOT WORKING IN MASTER.