Permit: T01CM02233

Parcel: 137338110

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/27/2001 FRAMING Approved IVRS - Inspection 0000*
06/25/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) AT PREVIOUS INSPECTION SUPERINTENDENT WAS ADVISED THAT ROMEX CABLE HAD BEEN DAMAGED CRIMPED AND THAT THE CABLE SHOULD BE REPLACED AT THIS TIME THE CABLE HAS BEEN RE-SECURED PROTECTIVE COVER IS TORN, CURRENTLY DOES NOT COMPLY WITH NEC 336-16 AND 336-18 2) FLAT CABLES SHALL NOT BE STAPLED ON EDGE AND SHALL BE PROTECTED FROM PHYSICAL DAMAGE 3) RE-INSPECTION FEE DUE PRIOR TO NEXT INSPECTION
06/22/2001 FRAMING Denied 1) SHEARWALLS MISSING WEDGE ANCHORS 2) EXTERIOR GFCI AT REAR ROMEX NOT MADE UP 3) CRIMPED WIRE AT BEDROOM OPTION 4) SEAL PENETRATIONS AT SOLE PLATE SPLICES 5) TAPE SEAL WEATHER BARRIER WHERE TORN 6) DRAFT STOPS AT KITCHEN FURR DOWN 7) FIRE CHIMNEY FRONT COMBUSTIBLE MATERIAL NEEDS 1" CLEARANCE COMPLETE FRAMING
06/21/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) PREVIOUS INSPECTION REQUEST ITEMS NOT ADDRESSED
06/20/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) DRAFT STOP AND FIRE BLOCKS INCOMPLETE 2) CHIMNEY FLUE PIPE SPARK ARNESTER NOT INSTALLED PROPER COMBUSTIBLE MATERIAL CLEARANCE NOT PROVIDED 3) PROTECT ELECTRIC ROMEX WITHIN 1/4" OF STUD 4) RISER NOT INSTALLED