Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02217
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2001 | ELECTRIC - FINAL | Approved | ||
07/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*NEED LETTER (STAMPED ACT, NO. SIGNED & DATED FROM ELECTRICAL ENGINEER APPROVING THE ALTERNATE TYPE AND SIZE OF FEEDER CONDUCTORS. | |