Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 05/24/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1)MC CABLE TO SUPPORTED WITHIN 12" EACH BOX, APT 334-10 NEC.2)PLUG KO'S BOXES.3)MC CABLE TO BE SUPPORTED TO STRUCTURE NOT TIED TO OTHER CONDUITS ART 300-11B NEC.4)EMT CONDUIT TO BE SUPPORTED WITHIN 3' OF EACH BOX, ART 348-13 NEC. |