Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T01CM02201
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2001 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* | |
05/25/2001 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) SLAB WAS POURED WITHOUT INSPECTION | |
05/17/2001 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) MUST MAINTAIN MINIMUM OF 6' BETWEEN UNITS FINISHED EXTERIOR OR INSTALL FIRE WALLS UNABLE TO LOCATE REBAR IN FTG ON PLAN 2) PT CABLES NOT PER PLAN 3) ELECTRIC SERVICE PANEL REQUIRES 36" CLEAR WORKING SPACE IN FRONT OF PANEL MINIMUM 6' BETWEEN UNITS, 3' EACH SIDE OF UNITS TO PROPERTY LINE OR FIRE ROTING IS REQUIRED 4) NO OPENINGS INTO FIRE ROTED WALLS 5) PLANS DO NOT COMPLY WITH ASBUILTS 6) PLAN NOT REVIEWED FOR BUILDING WITHIN 3' OF PROPERTY LINE, SEE NOTE ON PLANS 7) RE-SUBMIT FOR PLAN CHECK APPROVAL |