Permit: T01CM02195

Parcel: 13705505D


Addresses:

1193 W IRVINGTON RD

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Date Description Inspector Results Comments
10/11/2001 BUILDING ABOVE CEILING Approved IVRS - Inspection 0000*
10/09/2001 BUILDING ABOVE CEILING Denied IVRS - Inspection 0935*1.) INSTALL CEIL GRID PER U.B.C. 2.) PAY REINSPECTION FEE @ 201 N STONE.
10/05/2001 BUILDING ABOVE CEILING Denied IVRS - Inspection 0999*INSTALL CEILING GRID PER UBC 25-2. 1.) REMOVE SCREWS FROM TRACK.
10/04/2001 BUILDING ABOVE CEILING Denied IVRS - Inspection 0999*PLEASE INSTALL CEIL GRID WIRES ACCORDING TO UBC 25.