Permit: T01CM02189

Parcel: 137338780


Addresses:

1911 W BAGLEY WY

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/05/2001 FRAMING Approved IVRS - Inspection 0000*
07/03/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE A 30 INCH WORK PLATFORM FOR ENTIRE SIDE OF AIR HANDLER SEE SHEET M1 NOTE #3 2) PROVIDE SCREENED VENTS IN GARAGE FOR HI AND LOW COMBUSTION AIR 3) TRANSFER DUCT NOT INSTALLED AS PER PLAN MASTER BEDROOM 4) PROVIDE BLOCKING BETWEEN RAFTERS UNDER PLATFORM TO PROTECT FROM LATERAL ROTATION 5) REFRIGERENT LINE AND LIQUID LINE NOT COMPLETE 6) FHA STRAP AT OVER KNOTCH MISSING NAILS AT REFRIGERENT LINE, 3 PER SIDE PER STRAP 7) ELECTRIC METAL BOXES NOT SECURED OR GROUNDED TWO LOCATIONS
06/28/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) NOT READY FOR INTERMEDIATE INSPECTION