Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T01CM02173
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
08/23/2002 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) NEED TO SEE DOUBLE WALL VENT FROM WATER HEATER INSTALLED. 2.) CORRECTIONS NOT MADE ON DRYER VENTS. 3.) STRAP FLEX DUCT UP OFF OF LIGHTS & GRID. FINISH HOOKING UP FLEX DUCT. 4.) INSTALL EXHAUST FAN IN STORAGE CLOSET. RECALL FOR INSPECTION. |