Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/27/2001 FRAMING Approved IVRS - Inspection 0000*
06/25/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE EAVE VENTS AS PER PLAN 2) INSTALL DAMPER AT MASTER BATHROOM EXHAUST FAN 3) REMOVE COMBUSTIBLE MATERIAL FROM TYBE B FLUE PIPE VENTS 4) EXPANSION BOLTS MISSING AT #4 SHEARWALLS 5) FIRE BLOCK INSTALLATION INCORRECT SEE UBC SEC 708.2.2 AND 708.2.1 6) PROVIDE EXPANSION BOLT WHERE ANCHORS EXCEED 48 INCHES ON CENTER AS PER PLAN 7) LOOSE RISER AT HUB CONNECTION SHOULD BE WRENCH TIGHT 8) CLEAN AND EXCAVATE TRENCH 24 BELOW FINISH GRADE