Permit: T01CM02159

Parcel: 111023090


Addresses:

3129 E SAMPRAS LN

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/04/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/30/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTES 1.) DOWNSTAIR: SUPPORT ROMEX RUNNINGS ALONG BLOCK WALL EVERY 4 1/2 PER N.E.C. 2.) SUPPORT ROMEX WITHIN 12" EACH TERMINATION CAN LTS, 3.) EXHAUST FAN NOT CONNECTED IN BATHROOM. 4.) UPSTAIRS: SUPPORT ROMEX ALONG BLOCKWALL, 5.) PUSH IN PLASTIC GROMMETS NOT ALLOWED IN PANCAKE BOXES, MUST HAVE CLAMP TYPE CONN, 6.) EXHAUST FANS NOT CONNECTED. 7.) ALSO NOT THAT ROUND METAL BOXES USED ARE NOT APPROVED FOR CEILING FANS. 8.) GAS PIPING NOT BONDED.