Permit: T01CM02157

Parcel: 133541760

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM02157

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2001 FRAMING Approved IVRS - Inspection 0000*
07/02/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) NEED PROPER CLEARANCE AT FURNACE FLUE 2ND FLOOR
06/29/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) LOW GAS PRESSURE TEST 2) TRANSITION FROM TYPE B GAS VENT SHOULD BE ABOVE WALL-IMPROPER CLEARANCE AT THIS TIME 3) DAMMAGED WATER HEATER FLUE AT GARAGE 4) X BRACE TRUSSES CENTER 2ND FLOOR 5) LEAK AT SHOWER PAN 2ND FLOOR