Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/03/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTIONS. |
| 06/26/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SUPPORT CONDUIT TO PANEL AS PER CODE 2. LABEL PANEL ON OUTSIDE COVER. 3.) FILL UNUSED OPENING I PANEL 4.) FINISH INSTALLING LIGHT TRIM. 5.) USE AN APPROVED CONNECTOR AT LIGHT FIXTURES 6.) CAN NOT USE SHEET METAL SCREW FOR GROUNDING. |