Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM02149
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*ALL ITEMS BELOW COMPLIED WITH. | |
| 09/03/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) LABEL ALL DISCONNECT SWITCHES AT SERVICE 2.) CORRECTLY LABEL PANELS AND DISCONNECT SWITCHES 3.) CLASS J FUSES INSTALLED IN GLASS "R" SWITCHES 4.) PANEL SCHEDULE "RC" DOES NOT MATCH LOADS DIFFERENT. "RD","RA","RB" | |
| 08/07/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 07/26/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*COMPLY WITH #5 | |
| 05/02/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PLEASE FINISH #4 & #5. | |
| 04/30/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK TO COVER PVC CONDUIT WITH CONCRETE ACROSS ROADWAY ROOF. 1.) IDENTIFY UNGROUNDED CONDUCTORS AS PER CODE BUILDING. 1. LABEL PANELS AND BREAKER PANELS & SERVICE 2. PROVIDE DISCONNECTING MEANS FOR WATER HEATER 3.) CAP ALL EXPOSED CONDUCTORS 4.) FINISH FLOOR BOXES. 5.) PLEASE PROVIDE REVISED PLANS AS DISCUSSED. OK TEMP C OF O. | |
| 04/29/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*ROOF 1.) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 2.) PLEASE LABEL DISCONNECTS. OK TEMP POWER FOR TEST. CLUB HOUSE. | |
| 04/25/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* |