Permit: T01CM02149

Parcel: 11611001L


Addresses:

2525 W ANKLAM RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM02149

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*ALL ITEMS BELOW COMPLIED WITH.
09/03/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) LABEL ALL DISCONNECT SWITCHES AT SERVICE 2.) CORRECTLY LABEL PANELS AND DISCONNECT SWITCHES 3.) CLASS J FUSES INSTALLED IN GLASS "R" SWITCHES 4.) PANEL SCHEDULE "RC" DOES NOT MATCH LOADS DIFFERENT. "RD","RA","RB"
08/07/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
07/26/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*COMPLY WITH #5
05/02/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE FINISH #4 & #5.
04/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO COVER PVC CONDUIT WITH CONCRETE ACROSS ROADWAY ROOF. 1.) IDENTIFY UNGROUNDED CONDUCTORS AS PER CODE BUILDING. 1. LABEL PANELS AND BREAKER PANELS & SERVICE 2. PROVIDE DISCONNECTING MEANS FOR WATER HEATER 3.) CAP ALL EXPOSED CONDUCTORS 4.) FINISH FLOOR BOXES. 5.) PLEASE PROVIDE REVISED PLANS AS DISCUSSED. OK TEMP C OF O.
04/29/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*ROOF 1.) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 2.) PLEASE LABEL DISCONNECTS. OK TEMP POWER FOR TEST. CLUB HOUSE.
04/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*