Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM02121
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000*THIS INSPECTION IS FOR LITING ONLY. A/C J BOXES ABOVE CLNG. ARE PENDING. THANKS. | |
07/31/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) HALL 2.) RMS FRONT CENTER 3. RMS EAST. | |
07/30/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*PARTIAL 1.) ALL ROOMS PER FLR. PLAN MARKED THIS DAY. | |
07/27/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*RECALL WHEN COMPLETED AND CHECKED 1.) CHECK EACH FIXTURE FOR A SEISMIC WIRES B END SCREWS OR EARTHQUAKE CLIPS. 2.) SUPPORT ALL MC CABLE RUNS IN EXCESS OF 6' LENGTHS. BE SURE SUPPORT WIRES ARE ATTACHED AT THE BOTTOM END TO THE CIELING GRID. 3.) DO NOT USE CIELING GRID SUPPORT WIRES TO SUPPORT MC CABLE. INSTALL SEPARATE WIRES. |