Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*THIS INSPECTION IS FOR LITING ONLY. A/C J BOXES ABOVE CLNG. ARE PENDING. THANKS. |
| 07/31/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) HALL 2.) RMS FRONT CENTER 3. RMS EAST. |
| 07/30/2001 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL 1.) ALL ROOMS PER FLR. PLAN MARKED THIS DAY. |
| 07/27/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*RECALL WHEN COMPLETED AND CHECKED 1.) CHECK EACH FIXTURE FOR A SEISMIC WIRES B END SCREWS OR EARTHQUAKE CLIPS. 2.) SUPPORT ALL MC CABLE RUNS IN EXCESS OF 6' LENGTHS. BE SURE SUPPORT WIRES ARE ATTACHED AT THE BOTTOM END TO THE CIELING GRID. 3.) DO NOT USE CIELING GRID SUPPORT WIRES TO SUPPORT MC CABLE. INSTALL SEPARATE WIRES. |