Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/20/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*FRONT PARTITION WALLS OK |
| 07/19/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) CENTER PURFITIONS AT FRONT OK TO ROCK. |
| 07/18/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO COVER THESE AREAS. HALLS EMERGENCY LIGHTS FRONT RECEPTION & OFFICE 1-2-3 FIRE ALARM PNL NOT IN. |
| 07/12/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) 12 CLASSROOMS AT CENTER & COPIER ROOM. LEAVE HALLWAY ONE SIDE OPEN. |
| 07/10/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO ROCK EAST DEMISING WALL AND EAST REAR THREE OFFICES CLASSROOMS |
| 07/05/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) WEST BACKWALL & CLASSROOM OK TO DRYWALL 2.) OK TO ONE SIDE BATHROOMS RECALL WHEN ROUGH IN IS COMPLETE 3.) CONFERENCE ROOM REAR CENTER OK |
| 07/03/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*THE INSTALLATION OF MC CABLE IN TO EMT IS PROHIBITED BY SECTIONS/ARTICLES 1.) 110-3 (A & B) LISTING REQUIRD MC INTO EMT & EMT USED AS RACEWAY FOR MC CABLE A FLEXIBLE CONDUIT 2.) 300LB TRANSITION REQUIRED FOR INDIVIDUAL CONDUIT SYSTEM. 3.) 300-17 PROVIDE PROOF HEAT WILL BE SISIPATED IN EMT SLEEVE SEE 110-3 LISTING REQUIRED 4.) 300-20 PROVIDE INFORMATION SHOWING THAT NO HEATING WILL OCCUR DUE TO FERRO MAGNETIC EFFECTS OF THEMETALLIC CABLE IN THE ELECETRICAL METALLIC CONDUIT. 5.) 300-37 NO CODE PROVISION INSTALLATION OF ONE WIRING METHOD MC IN/TO ANOTHER EMT. |