Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*THIS AKNOWLEDGES A LETTER FROM ARCHITECT OF RECORD.I WANT TO CLARIFY THIS AS FOLLOWS.HE STATES THAT IT SHOULD BE OBVIOUS THAT THE WALLS AND CEILINGS WERE NOT ONE <1> HOUR RATED ASSY'S AS BUILT.I AGREE WITH THIS AS WRITTEN.HOWEVER THSI COMB. FIRE SMOKE DAMPER DETAIL WAS SHOWN PENETRATING A RATED 1 HR. STRUCTURE.THERE WAS NOT A MODIFIED DRAWING INDICATING THE DAMPER IN A NON RATED WALL.THIS JOB IS APPROVED ACCEPTING DAMPER IN A NON RATED ASSY. AS PER DRAWING. | |
| 06/13/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*HAVE ARCH./ENGINEER PROVIDE WRITTEN STATEMENT THAT FIRE/SMOKE DAMPER WAS NOT INTENDED TO BE INSTALLED AS PER DRAWING <APPROVED> AND SPEC'S, AND THAT INSTALLATION AS EXISTS MEETS OWNERS INTENTION. | |
| 06/11/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1)EXISTING CEILING IN COMPT. ROOM IS NOT 1 HR.,LACHS 5/8" DRY WALL ON TOP SIDE.2)HAVE ENGINEER/ARCH PROVIDE DIRECTION.3)FIRE/SMOKE DAMPER DETAIL WAS NOT FOLLOWED AS PER SHT.M1 |