Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/14/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*THIS AKNOWLEDGES A LETTER FROM ARCHITECT OF RECORD.I WANT TO CLARIFY THIS AS FOLLOWS.HE STATES THAT IT SHOULD BE OBVIOUS THAT THE WALLS AND CEILINGS WERE NOT ONE <1> HOUR RATED ASSY'S AS BUILT.I AGREE WITH THIS AS WRITTEN.HOWEVER THSI COMB. FIRE SMOKE DAMPER DETAIL WAS SHOWN PENETRATING A RATED 1 HR. STRUCTURE.THERE WAS NOT A MODIFIED DRAWING INDICATING THE DAMPER IN A NON RATED WALL.THIS JOB IS APPROVED ACCEPTING DAMPER IN A NON RATED ASSY. AS PER DRAWING.
06/13/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*HAVE ARCH./ENGINEER PROVIDE WRITTEN STATEMENT THAT FIRE/SMOKE DAMPER WAS NOT INTENDED TO BE INSTALLED AS PER DRAWING <APPROVED> AND SPEC'S, AND THAT INSTALLATION AS EXISTS MEETS OWNERS INTENTION.
06/11/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1)EXISTING CEILING IN COMPT.
ROOM IS NOT 1 HR.,LACHS 5/8" DRY WALL ON TOP SIDE.2)HAVE ENGINEER/ARCH PROVIDE DIRECTION.3)FIRE/SMOKE DAMPER DETAIL WAS NOT FOLLOWED AS PER SHT.M1