Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T01CM02099
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2001 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
06/15/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) ALTERNATE HOLD DOWN IS NOT TIGHTENED DOWN 2) GABLE TRUSS, ON 2ND FLOOR DORMER, MUST BE STRAPPED TO INTERSECTING TOP PLATES 3) ONLY ATTACHMENT FOR DORMER WALLS ARE BOTTOM PLATES NAILED TO OSB ROOF DECKING BELOW | |
06/13/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) DO NOT RE-CALL UNTIL CORRECTIONS ARE MADE | |
06/11/2001 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) INSTALL ENGINEER APPROVED ALTERNATIVE HD AT SOUTHEAST CORNER 2) #5 SHEARWALLS REQUIRE AB'S 24" ON CENTER 3) ROOF NAILING WAS ON GOING AT TIME OF INSPECTION |