Permit: T01CM02083

Parcel: 10818717A


Addresses:

1890 E RIVER RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T01CM02083

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
08/15/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) OFFICE, RM # 120 BATT INSULATION NEEDS TO BE REPLACED IN POSITION. 2.) RM#125 COPPER REGRIG LINES INCONNECT WITH STEEL FRAMING.
07/18/2001 MECHANICAL - ABOVE CEILING Partial Approval OK TO SET TILES IN GRID.
07/16/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*FIRE DAMPER BOTTOM ANGLE.
06/20/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*COMB. FIRE/SMOKE DAMPERS AT RATED CORRIDOR,2ND FLOOR, SOUTH SIOLE>OK
OK FOR TEMP. C OF O.
06/18/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*