Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM02083
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/18/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | ||
07/16/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) DATA LAYING ON GRID 2.) NEED TO SEE ALL EXIT LIGHTS ON PLANS. | |
06/20/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* OK 2ND FLOOR CEILING *NEED LETTER FROM ENGINEER/ARCH REGARDING INSTALATION OF FIRE DAMPER POWER | |
06/18/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) DUCT FIRE SMOKE DAMPER ARE 120V RATED NEED TO SEE WIRING AND CONNECTIONS ON UNITS AND ON PLANS 2.) DATA CANNOT LAY ON CELING OR ACROSS ELECTRIC CABLES 3.) SUPPORT CONDUCT AS PER CODE 300-11 | |
06/17/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1)SUPPORT DATA AS PER CODE-CAN NOT LAY ON GRID ALSO FOLLOW 300-11. 2)SUPPORT FLEX AS PER CODE.3)SUPPORT CONDUIT AS PER CODE. |