Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM02072

Parcel: 11301101A


Addresses:

1349 E PRINCE RD

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/06/2001 FRAMING Approved IVRS - Inspection 0000*
10/29/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) EXTERIOR WALL FRAME DOES NOT OVERLAP AT CORNERS AS REQUIRED BY UBC SECTION 2326.11.2 OR IRC SECTION 602.3.2 2) 9 EACH LPI JOIST HAVE 2 1/2" HOLES DRILLED 8" FROM BEARING ENDS PROVIDE LPI INSTALLATION STANDARDS AND OR LPI ENGINEERS APPROVED REPAIR APPROVED BY CITY OF TUCSON 3) CS100-10" STRAPS MISSING FROM PORCH RAFTERS DETAIL D/1 4) GREAT ROOM NOT FRAMED PER ROOF FRAME PLAN. REQUIRES LPI'S AT 24" ON CENTER. HAS 6' X 8"'S AT 48" ON CENTER REVISE PLAN AND HAVE APPROVED 5) PROVIDE PROOF OF LEDGER CLIPS PER A/1 6) INTERIOR BEARING 2 X 4 WALL MUST BE FRAMED AT 16" ON CENTER C/1 7) MECHANICAL NOT PER PLAN-REVISE AND HAVE CITY OF TUCSON APPROVAL 8) MANY DUCTS RESTRICTED 9) GAS LINES NOT PROPERLY SUPPORTED OR SECURED 10) PROVIDE WHOLE HOUSE PWV WATER TEST 11) MASTER BATH TUB VENT CANNOT RUN HORIZONTAL UNTIL 6" ABOVE FLOOD RIM 12) PROVIDE CSS GAS LINE INSTALLATION STANDARDS 13) HTT22 REQUIRES 5/8" ANCHOR BOLT