Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/05/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 07/03/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BLOCK 3 SIDES ALL SUPPLY DUCTS 2) INSTALL DAMPERS AT EXHAUST FANS 3) PROVIDE DETAILS 6/SD3 AND 7/SD3 AT SHEAR TRANSFERS 4) BALLOON FRAME AT STAIR WALL WEST SIDE AND OR PROVIDE TRUSS AND FLOOR JOYCE CALC'S 5) INSTALL HOLDOWNS AT INTERIOR SHEARWALLS 6) DORMER VENTS NOT INSTALLED AS PER PLAN 7) PLATFORM NOT INSTALLED FOR WORK AND SERVICE TO FURNACE 8) STAIRWAY RUN AND LANDING LOOSE |