Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM02045
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
08/21/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) #14 AND 12 GROUND WIRES CANNOT BE DOUBLE TAPPED TOGETHER IN PANEL DOUBLE TAPPED WIRES MUST BE SAME SIZE EXTERIOR INSPECTION COMPLETE-ALL OK EXCEPT NOTED 1 AND 4 2) NO THERMOSTAT IN PLACE 3) ATTIC ACCESS LADDER INSUFFICIENT FOR USE BY 200 POUND PLUS PERSON 4) COMPLETE DRIVEWAY SLAB |