Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/18/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/10/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) STAIR HANDRAIL MUST RETURN TO AND TERMINATE PT WALL UBC SECTION 1006.9 AND IRC SECTION 305 |
| 12/06/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) STAIR REQUIRES HAND RAIL 34-38" ABOVE NOSING AND MUST RETURN TO WALL 2) SMOKE DETECTORS REQUIRED IN EACH EXISTING BEDROOM 3) A GAS SHUT OFF VALVE REQUIRED UPSTREAM OF GAS FURNACE UNION OR INSTALL A LEFT AND RIGHT HAND NIPPLE AND COUPLING 4) POOL ROOM WATER HEATER MISSING GAS VALVE AND GAS CONNECTOR |