Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 09/18/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRIC CIRCUIT TO STORAGE NOT PROPERLY SUPPORTED 2) NEW METALIC FLEX CONDUIT NOT ALLOWED OVER 6' 3) SUPPORT ALL ELECTRIC BOXES 4) GROUND ALL METAL ELECRIC BOXES 5) NON METALIC SHEATHED CABLE NOT ALLOWED TO BE EMBEDED IN MASONARY 6) APPROVED WIRED 110 VAC SMOKE DETECTOR REQUIRED IN BEDROOM 6) NO ELECTRIC MECHANICAL OR PLUMBING PLANS ON SITE 7) WIRE TRIPPED AT BEDROOM ENTRY SILL PLATE 8) FIREBLOCK DROP CEILING AT MASTER BATH DUCT SOFFIT 9) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFING 10) BATH GFCI CIRCUIT FOR LAV MUST BE 20 AMP 12 GAUAGE DEDICATED |